New EP series UPS paramaters Visit our on-line store
Three phrase Input-three phrase output |
|||||||
Rating capacity (VA) |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
Rating power (W) |
9KW |
13.5KW |
18KW |
27KW |
36KW |
54KW |
72KW |
Input |
|||||||
Input valtage range |
380/400/415Vac±15%, three phase input |
||||||
Input frequency range |
50/60 ±5HZ automatically indentify |
||||||
Power factor |
>0.8(without filter),can achieve unit power factor(have filter) |
||||||
Output |
|||||||
Rating output current |
15A |
23A |
30A |
45A |
60A |
90A |
120A |
Rating output voltage |
380/400/415Vac±1% |
||||||
Output frequency |
Automatically tack the input |
||||||
Output waveform |
Sine wave |
||||||
Frequency range |
50/60 ±0.05%HZ |
||||||
Power factor |
0.9(lag) |
||||||
Distortion |
Linear load<3%,No-linear load<5% |
||||||
Over load capability |
over load to 110%,125%,150%, can keep working 60min/10min/1min |
||||||
Peak factor |
3:1 |
||||||
Overall efficiency |
88% |
89% |
89% |
90% |
90% |
91% |
91% |
Convertion time |
|||||||
Main supply->BAT |
0ms |
||||||
Bypass |
|||||||
Rating voltage |
380/400/415VAC |
||||||
Voltage range |
UP +15%,DOWN -20% |
||||||
Rating frequency |
50/60 Hz automatically indentify |
||||||
Frequency range |
±2% |
||||||
Convert time |
0ms/1ms |
||||||
Over load capability |
15 times rating current (10ms), 5times rating current (5s) |
||||||
Battery |
|||||||
Battery voltage(VDC) |
320—490VDC:380VAC,30 cells batteries;400 VDC,31 cells batteries;410VDC 32 cells batteries |
||||||
Panel display |
|||||||
LED |
Indicate the input,,inverter,bypass,battery and output status |
||||||
LCD |
Display the input/output voltage,frequency,power,power factor;battery Voltage,current,status;Load status,UPS status,history data,seting paramater |
||||||
Communication |
|||||||
Communication interface |
Dry contact,RS232,RS485,SNMP card |
||||||
Working enviroment |
|||||||
Working temperature |
0~40℃ |
||||||
Working humidity |
0~95% no condensation |
||||||
Restore temperature |
-25 ℃~55℃ |
||||||
Noise(range in 1M) |
<63dB |
<67dB |
|||||
Options Harmonic filter,Snmp adapter,Bapass current-inductance |
|||||||
Standard: YD/T1095 |
Application:
Small-medium internet data center, telecom and other mission-critical applications
Ordering information
1. input & output NO. : dual or single
2.input & output phase:
1 phase, 220VAC input, 1 phase 220VAC output
3 phase, 380VAC input, 3 phase 220VAC output
3 phase, 4 wires 380VAC input, 3 phase 4 wires 380VAC output
3.Load capacity:kVA
4.DC voltage:VDC
5.Feeder ark:Need or No need?
6.SNMP card:Need or No need?
7.Isolation transformer: Need or No need?
8.Back up time requirements:Hrs