10-80kVA Mid-star 2000 series UPS

10-80kVA Mid-star 2000 series UPS
  • Country of origin : China
  • Brand : TMEIC
  • Model : 2233B
  • Certification : IEC
  • Warranty : 3 years
  • Packing : wooden
  • Delivery time : 90 working days
  • Payment terms : T/T,L/C
  • Loading port : Guangzhou
  • MOQ : 1 PCS
Mid-star 2000 series UPS |uninterruptible power supply pdf,uninterruptible power supply ,uninterruptible power supply price,best uninterruptible power supply ,uninterruptible power suppliesuninterrupted power supplies ,uninterruptable power supplies ,uninterruptible power supply system 

Detailed

Send e-mail to electway@yahoo.com for more details

TMEIC Brand Mid-star 2000 series UPS products are OEM products assembled in China with Mitsubishi components.The capacity range is 10kVA to 80kVA.
 

Mitsubishi 2233B Series / TMEIC Midstar2000 Series UPS

 
Power Specifications

 

Rated output
Power
Input voltage
3 Æ / 4 wire
Output voltage
3 Æ / 4 wire
10kVA/8kW
20kVA/16kW
30kVA/24kW
40kVA/32kW
50kVA/40kW
60kVA/48kW
80kVA/64kW
380
380
380
380
380
380
380
380
380
380
380
380
380
380
 
UPS Module Information

 

UPS
(kVA)
CABLE
ENTRY
WIDTH
(mm)
DEPTH
(mm)
HEIGHT
(mm)
WEIGHT*
(kg)
HEAT LOSS @ 380V(kcal/hr)
10
BOTTOM
500
800
1000
160
722
20
BOTTOM
500
800
1000
165
1,361
30
BOTTOM
500
800
1000
170
2,041
40
BOTTOM
800
800
1200
460
2,393
50
BOTTOM
800
800
1200
460
2,991
60
BOTTOM
800
800
1200
500
3,590
80
BOTTOM
800
800
1200
550
4,786
* Including batteries

Specifications

 

Rated Output kVA
10
20
30
40
50
60
80
Rated Output kW
8
16
24
32
40
48
64
AC INPUT CHARACTERISTICS
Configuration
3 phase, 4 wire
Voltage
380/220 V    +15% ~ -55%
Frequency
50 Hz ± 5%
Reflected Current THD
3% typ. at 100% load; 5% typ. at 50% load
BATTERY
Nominal Voltage
576 V dc
AC OUTPUT
Configuration
3 phase, 4 wire
Voltage
380/220 V
Voltage Stability
±1%
Frequency
50 Hz
Frequency Stability
±0.01% in free running mode
Power Factor
0.8 nominal
Power Factor range
0.8 ~ 1.0 lagging (within output kW rating)
Voltage THD
2% typical THD at 100% Linear Load
4% typical THD at 100% non-linear load
Transient Response
±3% typical at 100% load step
±1% typical at loss/return of AC power
±3% typical at load transfer to/from static bypass
Transient Recovery
16.7 ms
Voltage Unbalance
2% typical at 100% unbalanced load
Phase Displacement
1deg. typical at 100% load
Inverter Overload
150% for 1 minute
System Overload
150% for 1 minute, 1000% for 1 cycle (with bypass available)
Bypass Overload
150% for 1 minute, 1000% for 1 cycle
Crest Factor Capabilities
3:1
ENVIRONMENTAL
Cooling
Forced Air
Operating Temperature
2°F ~ 104° F (0° C ~ 40° C). Recommended 59° F ~ 77° F (15° C ~ 25° C)
Relative Humidity
5% ~ 95% Non Condensing
Altitude
0 ~ 1500m No De-rating
Location
Indoor (free from corrosive gases and dust)

 