TMEIC Brand Mid-star 2000 series UPS products are OEM products assembled in China with Mitsubishi components.The capacity range is 10kVA to 80kVA.
Mitsubishi 2233B Series / TMEIC Midstar2000 Series UPS
Rated output
Power
|
Input voltage
3 Æ / 4 wire
|
Output voltage
3 Æ / 4 wire
|
10kVA/8kW
20kVA/16kW
30kVA/24kW
40kVA/32kW
50kVA/40kW
60kVA/48kW
80kVA/64kW
|
380
380
380
380
380
380
380
|
380
380
380
380
380
380
380
|
UPS
(kVA)
|
CABLE
ENTRY
|
WIDTH
(mm)
|
DEPTH
(mm)
|
HEIGHT
(mm)
|
WEIGHT*
(kg)
|
HEAT LOSS @ 380V(kcal/hr)
|
10
|
BOTTOM
|
500
|
800
|
1000
|
160
|
722
|
20
|
BOTTOM
|
500
|
800
|
1000
|
165
|
1,361
|
30
|
BOTTOM
|
500
|
800
|
1000
|
170
|
2,041
|
40
|
BOTTOM
|
800
|
800
|
1200
|
460
|
2,393
|
50
|
BOTTOM
|
800
|
800
|
1200
|
460
|
2,991
|
60
|
BOTTOM
|
800
|
800
|
1200
|
500
|
3,590
|
80
|
BOTTOM
|
800
|
800
|
1200
|
550
|
4,786
|
Specifications
Rated Output kVA
|
10
|
20
|
30
|
40
|
50
|
60
|
80
|
Rated Output kW
|
8
|
16
|
24
|
32
|
40
|
48
|
64
|
AC INPUT CHARACTERISTICS
|
|||||||
Configuration
|
3 phase, 4 wire
|
||||||
Voltage
|
380/220 V +15% ~ -55%
|
||||||
Frequency
|
50 Hz ± 5%
|
||||||
Reflected Current THD
|
3% typ. at 100% load; 5% typ. at 50% load
|
||||||
BATTERY
|
|||||||
Nominal Voltage
|
576 V dc
|
||||||
AC OUTPUT
|
|||||||
Configuration
|
3 phase, 4 wire
|
||||||
Voltage
|
380/220 V
|
||||||
Voltage Stability
|
±1%
|
||||||
Frequency
|
50 Hz
|
||||||
Frequency Stability
|
±0.01% in free running mode
|
||||||
Power Factor
|
0.8 nominal
|
||||||
Power Factor range
|
0.8 ~ 1.0 lagging (within output kW rating)
|
||||||
Voltage THD
|
2% typical THD at 100% Linear Load
4% typical THD at 100% non-linear load
|
||||||
Transient Response
|
±3% typical at 100% load step
±1% typical at loss/return of AC power
±3% typical at load transfer to/from static bypass
|
||||||
Transient Recovery
|
16.7 ms
|
||||||
Voltage Unbalance
|
2% typical at 100% unbalanced load
|
||||||
Phase Displacement
|
1deg. typical at 100% load
|
||||||
Inverter Overload
|
150% for 1 minute
|
||||||
System Overload
|
150% for 1 minute, 1000% for 1 cycle (with bypass available)
|
||||||
Bypass Overload
|
150% for 1 minute, 1000% for 1 cycle
|
||||||
Crest Factor Capabilities
|
3:1
|
||||||
ENVIRONMENTAL
|
|||||||
Cooling
|
Forced Air
|
||||||
Operating Temperature
|
2°F ~ 104° F (0° C ~ 40° C). Recommended 59° F ~ 77° F (15° C ~ 25° C)
|
||||||
Relative Humidity
|
5% ~ 95% Non Condensing
|
||||||
Altitude
|
0 ~ 1500m No De-rating
|
||||||
Location
|
Indoor (free from corrosive gases and dust)
|