Efficient, stable & maximize output power
High-power density modular design, supporting N + X parallel redundancy and cabinet in parallel, simple and fast to maintain, convenient and flexible to expand capacity
Advanced MPPT maximum power point tracking technology, compare with PWM pulse width modulation, increasing power generation up to 30%, in case of same power generation, it can save up to 30% solar panels
Extra wide input voltage range provides more flexible access solutions of solar panels
Perfect protection design, safe and reliable
Hot-swap modules with safety switch, and quick disconnection technology provides security guarantees
Input and output over voltage, under voltage, module failure, reverse polarity, anti-polarity, over-temperature protection function protect equipment perfectly
Intelligent battery management system
Choosing best charging mode according to the battery charging status, prolong battery life
Overcharge and over discharge protection functions send sound & light alarm timely, starting responsible protections automatically
Friendly human-machine interface, easy to use
Large touch screen LCD display, real-time graphic visual display operating status at a glance
Data storage device alarm and warning information stored for easy troubleshooting
Model(HSC-L) | 20kW | 30kW | 40kW | 50kW | 60kW | 70kW | 80kW |
Number of input string | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Max input power/current per string |
11kW/45A | ||||||
Input voltage range | 250~450Vdc | ||||||
Rated power(kW) | 20kW | 30kW | 40kW | 50kW | 60kW | 70kW | 80kW |
Output current(A) | 100 | 150 | 200 | 250 | 300 | 350 | 400 |
Output voltage range | 192~264Vdc, default: 240Vdc | ||||||
Model(HSC-M) | 30kW | 45kW | 60kW | 75kW | 90kW | 105kW | 120kW |
Number of input string | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Max input power/current per string |
15.5kW/35A | ||||||
Input voltage range | 430~650Vdc | ||||||
Rated power(kW) | 30kW | 45kW | 60kW | 75kW | 90kW | 105kW | 120kW |
Output current(A) | 80 | 120 | 160 | 200 | 240 | 280 | 320 |
Output voltage range | 310~420Vdc, default: 380Vdc | ||||||
Model(HSC-H) | 40kW | 60kW | 80kW | 100kW | 120kW | 140kW | 160kW |
Number of input string | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Max input power/current per string |
20.5kW/70A | ||||||
Input voltage range | 150~420Vdc | ||||||
Rated power(kW) | 40kW | 60kW | 80kW | 100kW | 120kW | 140kW | 160kW |
Output current(A) | 80 | 120 | 160 | 200 | 240 | 280 | 320 |
Output voltage range | 336~460Vdc, default: 430Vdc | ||||||
Same Data | |||||||
Ripple | ≤500 mVp-p | ||||||
Efficiency | ≥96.0% | ||||||
Accuracy of MPP tracking | 0.999 | ||||||
Accuracy of voltage | ≤±1.0% | ||||||
Dynamic response | 25~50~25% or 50~75~50% load, 0.1A/us; period 4ms | ||||||
Consumption | ≤20W | ||||||
Noise | ≤60dB(A) | ||||||
Cooling | Force cooling | ||||||
Degree of protection | IP20 | ||||||
Communication | RS485 | ||||||
Storage function | Max 200 items at monitor module | ||||||
Storage/Operation temp. | -40~+70℃/-20~+55℃ (+55~+65℃ derating to 80%) | ||||||
Environment temperature | 0~95%, non-condensing | ||||||
Altitude | 0~4000m (decrease 1℃ per 200m above 2000m) | ||||||
Dimension (W*D*H mm) | 600*600*1400 | ||||||
Weight (Kg) | 115 | 130 | 145 | 160 | 175 | 190 | 205 |