Voltage Variation
■ Standard Voltage 3Phase 4 Wires
380V
■ Voltages Available 3Phase 4 Wires
380, 400, 415 and 440V
Note: Outputs for optional voltages may differ from standard output mentioned above.
CONDITIONS & DEFINITIONS
Stand-by: Code: S
Applicable for supplying emergency power at varying load in the event of the normal utility power interruption.
Fuel stop power in accordance with ISO15550, ISO3046/1, JISB8002-1, DIN6271 and BS5514.
Overload: not allowed
Prime: Code: P
Applicable for supplying emergency power at varying load in the event of normal utility power interruption. 10% overload is allowed.
Fuel stop power in accordance with ISO15550, ISO3046/1, JISB8002-1, DIN6271 and BS5514.
Overload: 10% allowed
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard conditions.
Fuel rates: based on ASTM D975, BS2869 and on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/lb.) when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Specification
Model
|
power(KW)
|
engine model
|
cylinder(L)
|
bore
(mm) |
stroke
(mm) |
displacement(L)
|
capacity
(L) |
fuel consumption rate
(lir/hr) |
weight(kg) |
Dimension(mm) |
|
prime
|
standby
|
||||||||||
MGS660P1
|
600
|
660
|
S6R2-PTAA
|
6
|
170
|
220
|
30
|
92
|
170
|
5750
|
4023×1810×1953
|
MGS680P1
|
600
|
680
|
S12A2-PTA
|
12
|
150
|
160
|
33.9
|
120
|
175
|
6100
|
3996×1575×1959
|
MGS900P1
|
800
|
900
|
S12H-PTA
|
12
|
150
|
175
|
37.1
|
200
|
200
|
7800
|
4222×1756×2456
|
MGS1100P1
|
1000
|
1100
|
S12R-PTA
|
12
|
170
|
180
|
49
|
180
|
266
|
9100
|
4650×2100×2600
|
MGS
1200P1 |
1100
|
1200
|
S12R-PTA2
|
12
|
170
|
180
|
49
|
180
|
281
|
9600
|
4595×2156×2700
|
MGS1320P1
|
1200
|
1320
|
S12R-PTAA2
|
12
|
170
|
180
|
49
|
180
|
300
|
10000
|
4595×2156×2700
|
MGS1320P1
|
1200
|
1320
|
S16R-PTA
|
16
|
170
|
180
|
65.4
|
230
|
310
|
11100
|
5040×2486×2931
|
MGS1500P1
|
1300
|
1500
|
S16-PTA
|
16
|
170
|
180
|
65.4
|
230
|
330
|
11750
|
5382×2486×2931
|
MGS1680P1
|
1500
|
1680
|
S16-PTA2
|
16
|
170
|
180
|
65.4
|
230
|
418
|
12000
|
5382×2486×2931
|
MGS1800P1
|
1600
|
1800
|
S16-PTAA2
|
16
|
170
|
180
|
65.4
|
230
|
432
|
14400
|
5875×2392×3453
|
ENGINE STANDARD EQUIPMENT
Aftercooler
Turbocharger filter
Structure steel base
Crankcase breather
Charging alternator
Lubricating oil cooler
Fuel filters, full flow paper element
Fuel transfer pump, gear driven, plunger type
Electronic type governor
Jacket water pump, gear driven
Lubricating oil filter, full flow paper element
Lubricating oil pump, gear driven
Exhaust dry manifold
Radiator, blower fan, fan drive
Manual shutoff
24V DC electric starting motor
Type & Design
MGS SERIES 7310 GENERATORCONTROL PANEL
MGS standard 7310 programmable microprocessor control-automatic start/stop panel, generator breaker control, indicating the operational status and fault conditions; automatically shutting down the engine and indicating the engine failure by means of LCD display and LEDs on the front panel.
Controls & Monitoring
◆ Mode selection & start engine button with interlock key switch system
◆ Menu navigation button
◆ LCD display for: AC amperage-each phase and earth current, AC voltage-each phase and neutral, Frequency Hz, Operation hours run, Lub. Oil pressure, Cooling water temperature, Generator Load kW/kVA/kVar, Generator Load kWh/kVAh/kVarh
◆ Operation status LED indicators
◆ CB control buttons
◆ Mute/Lamp test button
◆ Voltage adjuster
◆ Speed adjuster
◆ Emergency stop pushbutton
◆ Provided 5 outputs for status as standard equipment (Programmable 8 outputs available as option)
Safety Shutdown Protection and LED Indicators
High engine temperature, Low oil pressure, Fail to start, Generator Over Speed/Frequency,
Generator Under Speed/Frequency
Generator High Voltage, Generator Low Voltage, Oil pressure sender circuit, Loss of Speed signal , Emergency stop,
High crankcase internal pressure (MGS-C continuous only)
Mounting
Fabricated cubicle mounted on individual bracket with anti-vibration isolator
Electrical Design
In accordance with BS EN 60950 Low Voltage Directive, BS EN 61006-2 and 61006-4 EMC Directive. The optional interface can provide real time diagnostic facilities.
Generator Control Panel Description
■ 3 position operation mode control key switch
(ACTIVE, PANEL LOCK, STOP/RESET)
■ Manual button
■ Stop/Reset button (Manual only)
■ Auto button
■ Mute/Lamp test button (Manual only)
■ CB open button (Manual only)
■ Voltage adjusting trimmer
■ CB close button (Manual only)
■ Speed adjusting trimmer
■ Start engine button (Manual only)
■ Emergency stop pushbutton
■ LCD display accessed by scroll pushbutton
Generator volts L1-N, L2-N, L3-N
Engine cooling water temperature (°C & °F)
Generator volts L1-L2, L2-L3, L3-L1
Battery volts
Generator amps L1, L2, L3
Engine hours run
Generator Earth Current
Generator Load kW, kVA, kVar
Generator Frequency Hz
Generator Load kWh, kVAh, kVarh
Engine speed RPM
Power Factor
Engine oil pressure (PSI & Bar)
■ Visual indicators on LCD display
Shutdown alarm
Generator high current
Warning alarm
Over voltage (AC)
High coolant temperature
Under voltage (AC)
Low oil pressure
Over voltage (DC)
Charge fail
Under voltage (DC)
Over-speed
Auxiliary indication
Under-speed
Auxiliary alarm (warning or shutdown)
Electrical trip
Common alarm
Fail to stop
Over frequency
Under frequency
■ Visual indication alarm and automatically shutdown
High engine temperature
Over frequency
Low oil pressure
Under frequency
Fail to start
Oil pressure sender open circuit
Over-speed
Loss of speed signal
High voltage
High Crankcase internal pressure (MGS-C Continuous only)
Low voltage
Emergency Stop
■ Operation status indicated by LED
Remote start present
Lubrication oil filter clogged
Generator ready
Electrical trip
■ Pre-Programmed Starting Unit
Automatic start/stop sequence timing and delay systems configured
via MS-Windows based software.