Electway Electric

Download

Contact Us

Position: Home > Download > File Download
File Download

  • File Name

    Santak 3C3 EX 20-80K UPS User manual

  • Update Time2016-12-05 17:50:32
  • File Download Click on the download
  • DescriptionSantak 3C3 EX 20-80kVA UPS User manual

 

Item 3C3 EX 20KS ISO 3C3 EX 30KS ISO 3C3 EX 40KS ISO 3C3 EX 60KS ISO 3C3 EX 80KS ISO
Rated power 20kVA/16kW 30kVA/24kW 40kVA/32kW 60kVA/48kW 80kVA/48kW
Input Voltage 210-475VAC
Frequency 40-70Hz
Phase 3 pahse(L1+L2+L3+N+G)
THD I 3%
input PF >0.99
Dual AC input Sopport
Battery Type Valve regulated lead acid battery (VRLA) 
Back up time According the capacity of the battery you select
Output Voltage 380/220VAC
Frequency ,50/60Hz
Phase 3 pahse(L1+L2+L3+N+G)
output PF 0.8
over-load capacity 125% 10min
150% 1min
Efficiency Commercial power  93% 94%
Battery mode 93% 94%
ECO mode 98%
Display LCD English/Chinese simplied
input&output voltage,current,frequency,faulty alarm
LED run mode
Fan automatic adjustable yes
Alarm device Buzzer sound and light
Communication  RS232,AS400,RS485,Service,EPO,battery temperature compensate port
environment temperature 0-40°C
humidity ≤95%(0-40°C±2,No condensation )
Weight Net weight 82/208kg 110kg/275kg 114kg/314kg 282kg 306kg
Gross weight 122kg/248kg 160kg/325kg 164kg/364kg 356kg 380kg
Dimension WXDXH 420X630X956 470X710X1150 600X8001150
Standard EMC:GB7260.2/IEC26040-2    GB/T17626.2-5 IEC61000-4-2~5

Share on:

 

Hits:  UpdateTime:2016-12-05 17:50:32  【Printing】  【Close
Online 
Email to us
Feedback